MSK-SDA-1005F is a large recirculating chiller designed for the Small Drying Room MSK-ADR-1500EP40-LD, and large induction melders
SPECIFICATIONSÂ
| Power Supply |
AC 208 -240V; Three-Phase; 60 Hz |
| Power Input |
- Maximum Power: 5.2 KW
- Operating current: 16 A Maximum
|
| Cooling Capacity |
14.5 KW or 12,470 Kcal/h or 49.5 K BTU |
| Compressor |
- Rotary Compressor
- Input Power: 3.75 KW
- Operating current: 10.8 A
|
| External Recirculating Pump |
- Water Pressure: 20-meter ( 28 PSIG)
- Water Flow Rate: 8 m^3 / hr;Â 133Â L/min ( 35GPM)
|
| Refrigerant |
R22 |
| Temperature Control |
5 ~ 30 °C |
| Temperature Accuracy |
± 1 °C |
| Heating Exchanger |
Aluminum Foil Fin + Copper Pipes + External Rotary Venting Fan |
|
Water Tank
|
- 50 Liters ( 13.2 Gallon)Â made of stainless steel (Â
- The water chiller should not be connected to a system with a capacity more than the tank's capacity.
- Use anti-crossion coolant instead of water for a longer service life.
- Do not use deionized water as the cooling agent; DI water may cause the copper pipe to corrode, mainly pitting, and leak over time.
|
| Overall Dimensions |
1,300 mm (L) x 600 mm (W) x 1,250 mm (H) |
| Net Weight |
220 kg |
Compliance
|
- CE approval
- NRTL or CSA is available upon request at extra cost, please contact our sales representatives for a quote.Â
|
| Application Notes |
- The use of tap water is prohibited.
- Distilled water is preferred to be used in a water chiller.
- Please connect the chiller water outlet to the equipment water inlet and the chiller water inlet to the equipment outlet. Otherwise, the water flow sensor on the equipment may fail to work due to the wrong water flow direction
|